Airtest TR2000 CO Lon (LonWorks®)

$565.00

AirTest Electrochemical CO Transmitter – Air Quality Sensor

Description

CO And Parking Garages Airtest TR2000-CO-Lon (LonWorks®)

Airtest TR2000-CO-Lon.  Most local codes require a very high rate of ventilation (1.5 to 2 cfm.sq ft) in enclosed parking and areas involving vehicle repair and operation. This must be provided during all hours of use. A Carbon Monoxide sensor can reduce fan energy costs by acting as an occupancy sensor for automobiles. Most codes allow fans to be intermittently operated as long as levels do not exceed 30 or 50 ppm CO (check your local code).

ALL AIRTEST GAS SENSORS ARE PRECALIBRATED AT THE FACTORY.  NO ADDITIONAL CALIBRATION IS REQUIRED.

The TR-2000 delivers all the advantages of electrochemical sensing in a durable, long life (5 year) package that is priced to compete against less accurate MOS/Solid State sensors. The loop powered sensor delivers a linear 4-20 ma output that is easily integrated into any building control, ventilation or alarm application. The low profile design can be attached to any single gang electrical box and features a low cost replaceable sensor element.
– LonWorks® FTT-10 free topology transceiver.
– Five year life
– High accuracy sensor, +/- 5% of measurement.
– 0-200 ppm range.
– Low cost replacements sensor elements minimizes long term operating costs.

Sensing Method: Electrochemical

Approval: CSA/NRTL (UL Equivalent), UL2075 (Sensor)

Sensor Rated Life: 5 yearsTemp

Operating Conditions: -4 to 122º F (-20 to 50ºC),Humidity

Operating Conditions: 0 to 90% RH

Storage Conditions: -40 to 158ºF (-40 to 70ºC)

Performance

CO Measurement Range: 0-200 ppm (factory adjustable to 500 ppm)

Repeatability&Linearity: +/- 5% of measured value

Accuracy: +/- 2 ppm

Annual Drift: <±5% of measured value per year.

Recommended Calibration: 2.5 years

Response Time: T90 = <1 minutes (diffusion)Warm Up Time: < 2 minutes

Power: Input: 18-24 VDCPower Consumption: 150 mA max

Analog Outputs Adjustment: Span & ZeroOutput Signal: 4 – 20 mA & LonWorks®Terminal Wire Size: 16 – 22 AGW

Model CT1000-CO

Controller

  • Temp Range: :-4 to 122ºF (-20 to 50ºC)
  • Integrated high and low concentration relays(5A)
  • Power options: 24 VAC, 115 VAC, 220VAC
  • User adjustable delay for on-time (up to 30 minutes).
  • Measures: 0- 400 ppm
  • Calibration: 1 year recommended

Model TR2000-CO

  • Temp Range: :-4 to 122ºF (-20 to 50ºC)
  • Output: 4-20 mA (loop powered)
  • Power: 12-30 VDC
  • Measures: 0- 200 ppm
  • Calibration: 1 year recommended

Model TR2000-CO-Lon

  • Same performance as TR2000-CO above.
  • LonWorks® Network Variabies: nviRequest, nciMaxStsSendT, nvoStatus
  • LonWorks® Sensor Variables: nvoSensorValue (% of range), nvoSensorInv, nciMiniDelta, nciSnsrSmplRate

Model TR2000-CO-W

  • A wireless communicating sensor used with the CT5000 wireless ventilation control system.

 

PDFTR2000 manual.jpg PDFTR2000 Spec.jpg